Video: How to generate a Meter Configuration report using ION Setup
Issue
User may need to generate a Meter Configuration report or Event Log in ION Setup
Product Line
PowerLogic Power Meters
ION Power Meter
Environment
ION Setup
Resolution
For ION Meters:
- Select the desired ION Meter
- Double-click on Setup Assistant to launch Setup Assistant
- Select Reports
- To generate a Meter Configuration report, double-click on Meter Configuration
- To save the file in text format, click Save As...
- Select a file location, type desired file name, and click Save
For PowerLogic Meters
- Select the desired PowerLogic Meter
- Double-click on Reports
- To generate a Meter Configuration report, select Meter Configuration and then click Display
- To save the file in text format, click Save As...
- Select a file location, type desired file name, and click Save