Video: How do I use UMAC V2.2 to convert a Unity Quantum application to an M580 application?

Issue:
Converting a Unity Quantum application to an M580 application using the UMAC v2.2 tool

Product Line:
Quantum, Unity Pro, M580, 1MMCSVCZMSXAZZ,

Resolution:
In order to use the the UMAC conversion utility to migrate a Unity quantum application to M580, the user must meet the following criteria.

Prerequisites:
1: The user must have Unity Pro XL =>V12.0 installed on his PC
2: UMAC V2.2 will only accept a Quantum ZEF file created in Unity Pro XL => V12.0
3: Install UMAC and select upgrade to "Standard" mode.

Conversion process
1: Launch the UMAC converter using the "Run as Administrator" option.
2: When prompted, point to the Quantum ZEF file you wish to convert to M580
3: Execute the conversion when prompted by UMAC.
4: Save the converted ZEF file.
5: Generate conversion report from within UMAC.


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше

Досліджуйте більше

Потрібна допомога?

Почніть тут!

Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

Звернутися до служби підтримки

Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

Де придбати?

Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

Переглянути відповіді на поширені запитання

Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.