ATV212: How do I wire and program an ATV212 for 3-wire control AND speed reference from the face of the drive?
Issue:
Wants to wire and program a ATV212 for 3-wire control AND speed reference from the face of the ATV212 drive.
Product Line:
Altivar 212
Environment:
All
Cause:
Setup assistance
Resolution:
1. Wire F terminal for forward Normally Open (NO), momentary close to Start
2. Wire R terminal for Normally Closed (NC) Stop
3. Set Fnod to 3 --speed reference from the face of the drive
4. Set F111 to 2 --forward command on F terminal
5. Set F112 to 49 --3-wire control activated
Wants to wire and program a ATV212 for 3-wire control AND speed reference from the face of the ATV212 drive.
Product Line:
Altivar 212
Environment:
All
Cause:
Setup assistance
Resolution:
1. Wire F terminal for forward Normally Open (NO), momentary close to Start
2. Wire R terminal for Normally Closed (NC) Stop
3. Set Fnod to 3 --speed reference from the face of the drive
4. Set F111 to 2 --forward command on F terminal
5. Set F112 to 49 --3-wire control activated
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.