Is it possible to connect one earth leakage circuit breaker with multiple ATV12 drives? How should that work?
Issue:
Is it possible to connect one earth leakage circuit breaker with multiple ATV12 drives? How should that work?

Product Line:
Altivar Machines, Altivar 12

Environment:
All models and serial numbers

Cause:
Documentation

Resolution:
The earth leakage breaker could be used with up to two or three drives maximum.
But to avoid the random tripping of the breaker and blindness of earth leakage circuit breaker it is recommended to use the RCD (Residual Current Device) full immunized due to the perturbation Type A(si).
Usually we recommend using one RCD by drive as describe in our catalogue (link here: https://www.se.com/us/en/download/document/8800CT1301/ )

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:

Потрібна допомога?

  • Інструмент вибору продукту

    Швидко та легко знаходьте потрібні продукти й допоміжне обладнання для своїх завдань.

  • Розрахувати вартість

    Ставте свої запитання щодо продажів онлайн, і з вами зв’яжеться фахівець

  • Де придбати?

    Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

  • Довідковий центр

    Знайдіть усі необхідні ресурси для підтримки в одному місці.

  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміна продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • Ecostruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings