What can cause an bLF or brake control fault on the ATV630 and ATV930 Process drives?
Posible cause of a bLF Fault on ATV630/930.
Product Line:
ATV630 and ATV930 Process drives
Environment:
All
Cause:
Wrong setting of the parameter IBR (Brk Release Current)
Bad fluxing of motor ( 5*tr ).(tr = Rotor time constant).
Incorrect values of auto tuning (check in expert mode TRM).
Resolution:
| Principle: This fault appears when the brake logic is used and the conditions to open the brake are not present. If the brake release current (parameter IBR) is not attained after a delay (parameter BRR+100ms) or it is impossible to flux the motor during 5*tr ( tr = Rotor time constant ) then the fault appears. Probable cause: - wrong setting of the parameter IBR (Brk Release Current) Bad fluxing of motor ( 5*tr ).(tr = Rotor time constant). Incorrect values of auto tuning (check in expert mode TRM). Remedies: Check the drive/motor connections. Check the motor wending Check the IBR (current for brake opening while ascending) and IRD (current for brake opening while descending) settings. Check the setting of bEn (brake closing frequency) Check the parameter BRR Current ramp time ( only in expert mode ). |
Опубліковано для: Schneider Electric Україна




Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.