What can cause an CbF or circuit breaker error on the ATV630 and ATV930 Process drives?
Issue:
What can cause an CbF or circuit breaker error on the ATV630 and ATV930 Process drives?
Product Line:
Altvar Machines, Altivar Process Drives
Environment:
All models and serial numbers
Cause:
Inop motor circuit breaker
No mains voltage present
When running if the VBUS is less than USFH after the LCT monitor mains time out.
When stopped if the ULN is greater than 20vac the error will occur after the LCT Mains time out.
Resolution:
Check the mains voltage
Check the main circuit breaker to see if its tripped.
What can cause an CbF or circuit breaker error on the ATV630 and ATV930 Process drives?
Product Line:
Altvar Machines, Altivar Process Drives
Environment:
All models and serial numbers
Cause:
Inop motor circuit breaker
No mains voltage present
When running if the VBUS is less than USFH after the LCT monitor mains time out.
When stopped if the ULN is greater than 20vac the error will occur after the LCT Mains time out.
Resolution:
Check the mains voltage
Check the main circuit breaker to see if its tripped.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.