Issue
How do I find the number of requests serviced by the pocessor per mast cycle.
Product Line
M580, M340
Environment
Unity, Control Expert.
Resolution
This can be accomplished by viewing the system word %SW87 value with an animation table. This will provide the number of backplane requests being processed by the CPU per mast cycle.