On an ATV212, can the analog input be programmed for 0-10V to control 30-60Hz?
Issue:
Programming analog input for 0-10V to control 30-60 Hz on an ATV212 Drive.
Product Line:
Altivar 212
Environment:
All
Cause:
Wants 0-10V to equal 30-60Hz
Resolution:
Yes, this is accomplished by adjusting the scaling of the applicable analog input so that the drive knows that 0%=30Hz.
If you're using VIA: Adjust F201 to 0%, F202 to 30Hz, F203 to 100% and F204 to 60 Hz.
If you're using VIB: Adjust F210 to 0%, F211 to 30Hz, F212 to 100% and F213 to 60 Hz.
For details on accessing these parameters please see the FAQ on ATV212 Basic Programming.
Programming analog input for 0-10V to control 30-60 Hz on an ATV212 Drive.
Product Line:
Altivar 212
Environment:
All
Cause:
Wants 0-10V to equal 30-60Hz
Resolution:
Yes, this is accomplished by adjusting the scaling of the applicable analog input so that the drive knows that 0%=30Hz.
If you're using VIA: Adjust F201 to 0%, F202 to 30Hz, F203 to 100% and F204 to 60 Hz.
If you're using VIB: Adjust F210 to 0%, F211 to 30Hz, F212 to 100% and F213 to 60 Hz.
For details on accessing these parameters please see the FAQ on ATV212 Basic Programming.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.