Issue:
HCF [boards Compatibility] fault on an ATV340 series drive.
Product Line:
ATV340
Environment:
All
Cause:
The [Pairing password] PPi parameter has been enabled and an option module has been changed.
Resolution:
HCF [boards Compatibility] fault on an ATV340 series drive.
Product Line:
ATV340
Environment:
All
Cause:
The [Pairing password] PPi parameter has been enabled and an option module has been changed.
Resolution:
Refit the original option module.
Confirm the configuration by entering the [Pairing password] PPI if the module was changed
deliberately.