SBO upgrade process failed (SBO 1.8.x to SBO 1.9.x)

Upgrade failed when upgrading Automation Server from SBO version 1.8.x to 1.9.x

Log indicates:
(Device Administrator | View | Last Upgrade Log)
ERROR:        Exception encountered during database upgrade: StartUpMode UpgradeDatabase : RecoverableException: d:\dev\rb-rb-1.9.2-system\source\server\nsp_servers\csc\LonTypes\source\Lon2MapFileUtil.cpp(185) Invalid Data Error: Invalid_Data (0x10000) in module Impex(57). "Map data is too old for type: public.lon2.devicetemplates.pid90003A8200E90401. You need to run the Lon Repair command in the latest version of the workstation"
2019-04-10 07:14:02  INFORMATION:  Database upgrade time: 5.28889 seconds
2019-04-10 07:14:02  INFORMATION:  =============  End Configuration Database Upgrade  =============
Source version: 1.8.1.79 Target Version: 1.9.2.45

Steps
1. Upgrade Workstation and Automation Server to the latest available version (SBO 1.8.1.3600)
2. Connect with Workstation to Automation Server
3. Select Server, and right-click Advanced | Repair LonWorks configuration ...
4. Select Next to repair when indicated "Server needs to be repaired"
5. Finally upgrade to Version 1.9 using Device Administrator

Schneider Electric Україна

Вкладення
Start repair.PNG.png [120.18 KB]
repair01.PNG.png [37.8 KB]
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings