Чим ми можемо вам допомогти сьогодні?

SBO Struxureware Building Operation (now EBO EcoStruxure™ Building Operation) WorkStation crashes after value forced

Building Operation Workstation Error window notices:

- A problem has occurred in this application.
More info:
Could not load file or assembly 'SE.Script.Wrapper, Version=1.9.xx...
The system cannot find the file specified.

Cause:
File corrupted or lost

Steps:
1. Check folder : C:\Program Files (x86)\Schneider Electric StruxureWare\Building Operation 1.9\WorkStation\Script...
2. Delete/Rename original corrupted file: SE.Script.Compiler.Wrapper.dll
3. Run WorkStation Installation - Repair current version
4. Start WorkStation

Schneider Electric Україна

Вкладення
WS_installation_repaired.PNG.png [112.95 KB]
Workstation_Script_folder.PNG.png [83.55 KB]
WS_installation_repair.PNG.png [85.92 KB]
WS_crashinfo_ValueForced.PNG.png [157.81 KB]
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings