Чим ми можемо вам допомогти сьогодні?

What should be done if Ethernet communication for M241/251 logic controllers is interrupted after several hours?

This may come from READ_VAR / WRITE_VAR / READ_WRITE_VAR function blocks being called with an unreachable Server IP address.

For example:

If controller the Ethernet interface settings are:

    • Address: 192.168.0.50
    • Subnet mask: 255.255.255.0
    • Gateway: 0.0.0.0

and the READ_VAR function block tries to communicate with a Server at 192.168.10.20,

Then the Ethernet port may fail after several hours.

Workaround is :

  • Stop trying to reach Server which are not in the same subnet as the controller.
  • Check Ethernet cable status: ETH_R.i_wPortAIpStatus system variable value must be "DATA_EXCHANGE".
  • Use a gateway address (use controller address itself if there is no relevant gateway on the network): requests to unreachable Server will be redirected to the gateway
​

Schneider Electric Україна

Досліджуйте більше

Досліджуйте більше

Потрібна допомога?

Почніть тут!

Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

Звернутися до служби підтримки

Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

Де придбати?

Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

Переглянути відповіді на поширені запитання

Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.