Чим ми можемо вам допомогти сьогодні?
AS-P Modbus TCP Server do not provide data for HMI-STU Mobus Client
AS-P in version 1.9.4 can not respond for request which contain group of consecutive registers.
Exception Response FC03 - Illegal Data Address (Read Holding Register) - 00 00 00 00 00 06 FF 03 03 84 00 06 - 00 00 00 00 00 03 FF 83 02
(In this case client ask for 6 registers starting with register number 900)
Possible overwork:
1. Set HMI STU communication optimization mode to : Prefered Frame lenght = Minimum possible. Vijeo Designer, Equipment configuration.
2. Upgrade AS-P to version 2.0.3.45 (solution tested in ModScan32 tool)
Exception Response FC03 - Illegal Data Address (Read Holding Register) - 00 00 00 00 00 06 FF 03 03 84 00 06 - 00 00 00 00 00 03 FF 83 02
(In this case client ask for 6 registers starting with register number 900)
Possible overwork:
1. Set HMI STU communication optimization mode to : Prefered Frame lenght = Minimum possible. Vijeo Designer, Equipment configuration.
2. Upgrade AS-P to version 2.0.3.45 (solution tested in ModScan32 tool)
Опубліковано для: Schneider Electric Україна
Вкладення
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.