Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Why are the Trigger Alarm and Run Self-Test buttons grayed out for my unit on the SmartConnect web portal?

Issue:
The Trigger Alarm and Run Self-Test buttons are grayed out for my unit on the SmartConnect web portal.

Products:
SmartConnect Smart-UPS models SMT, SMTL, SMX, SRT

Cause:
SmartConnect control has been disabled on the Smart-UPS.

Solution:
If the Trigger Alarm and Run Self-Test buttons are disabled in the web portal, ensure that SmartConnect access is enabled on your Smart-UPS. From the LCD panel, navigate to Configuration > SmartConnect. The possible settings are Disable or Enable with Ctrl. Enable the setting with Ctrl. Once the change has been made, it will take 5 to 10 minutes to take effect. The web browser will need to be refreshed.



SmartConnect status

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Спільнота Schneider Electric
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings