How to make a momentary switch with a delay in Vijeo Designer?
Issue:
The momentary switch resets too quickly for the PLC to detect the state change from ON to OFF.

Product Line:
Vijeo Designer (all versions)

Resolution:
When the native Momentary On switch does not set a bit long enough for your application (possibly due to slower communications), it is possible to create your own Momentary On switch with a desired delay to wait before resetting the bit. Here we will provide a procedure on how to build this in Vijeo Designer.

1) On the Panel, draw a switch.
2) Set the Operation to "Bit"
3) First select the "Set" Operation
4) Assign your desired variable to the "Destination" Field. For this example, we will create BOOL01.
5) Press the "Add" button.
6) Next, set the Operation to "Delay".
7) In the Field "Delay Time", enter a static value or a mathematical expression. For this example, we will enter 2 (seconds).
8) Press the "Add" button.
9) Next, set the Operation to "Bit"
10) Select the "Reset" Operation
11) Assign BOOL01 to the "Destination" Field.

With the above procedure, you will create a Momentary On switch that sets a bit "BOOL01" for 2 seconds and then resets it afterwards


Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings