Чим ми можемо вам допомогти сьогодні?

What are the fan part numbers for ATV320?

The fan part numbers for the Altivar 320 (ATV320) vary depending on the specific drive model and rating.

To identify the correct fan part number:

  • Refer to the attached document, which provides a complete list of fan part numbers mapped to each ATV320 drive reference.


NOTE 1: Not all the fan kits are available for sale.  You can check with Schneider Electric Industrial Repair at 1-800-950-9550 to see if they can be specially purchased.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Вкладення

Досліджуйте більше

Серія:

Досліджуйте більше

Серія:

Потрібна допомога?

Почніть тут!

Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

Звернутися до служби підтримки

Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

Де придбати?

Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

Переглянути відповіді на поширені запитання

Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.