What is the speed limitation and bandwidth for ethernet backplane
The speed limitation for X-BUS backplane is 12Mbps and customer would like to know the speed limitation & bandwidth for Ethernet backplane. N/A Ethernet backplane is 100Mbps full duplex. The bandwidth for each slot is as following:
- Ingress rate limiting must be set to 0.1 Mbps for broadcast traffic.
- Ingress rate limiting must be set to 1 Mbps for all other traffic.
- Port egress rate limiting must not be set.
Опубліковано для: Schneider Electric Україна

