How is the Self Test accessed in the ATS22?
Issue:
Access Self Test in an ATS22.
Product Line:
Altistart 22
Environment:
All
Cause:
Troubleshooting
Resolution:
Access the Utility Menu by pressing the ESC and the UP arrow buttons at the same time.
Navigate to tESt and press ENT
Result
Good
BAd. Possible causes :
- Improper internal voltage,
- Checksum error,
- Disconnected keyboard,
- Disconnected heatsink thermal sensor,
- Disconnected bypass relay (frame size C).
Refer to the ATS22 User Manual for further details.
Access Self Test in an ATS22.
Product Line:
Altistart 22
Environment:
All
Cause:
Troubleshooting
Resolution:
Access the Utility Menu by pressing the ESC and the UP arrow buttons at the same time.
Navigate to tESt and press ENT
Result
Good
BAd. Possible causes :
- Improper internal voltage,
- Checksum error,
- Disconnected keyboard,
- Disconnected heatsink thermal sensor,
- Disconnected bypass relay (frame size C).
Refer to the ATS22 User Manual for further details.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.