Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
How to delete recipes at runtime on the Magelis HMI?

Issue:
Looking for options on how to delete recipes created or downloaded to the Magelis HMI at runtime.

Product Line:
Vijeo Designer (all versions)

Resolution:
In Vijeo Designer, there are a couple of ways in which we can delete a recipe during runtime on the Magelis HMI.

The first option is to make use of a "Delete" recipe button that you can drag onto the panel from the toolchest in Vijeo Designer. During runtime, when you select a recipe group and recipe, when you press the Delete button, it will delete the selected recipe from the list.

The second option is to write a script in an action or in a touch action script. The script will essentially write a value to the _RecipeDefaultControl.Operation variable. The value to trigger a delete is the value "16"

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings