Issue:
The ATV320 drives to trip on OSF faults on powerup?
Product Line:
ATV320
Environment:
All serial numbers
Cause:
Can not clear fault
Resolution:
To clear the OSF fault on powerup:
Set UrES [Mains voltage] to correct value of the line supply voltage.
Parameters described can be accessed by:
DRI- > CONF > FULL > FLT- > CLL
USb- [UNDERVOLTAGE MGT] > enter
UrES [Mains voltage] > enter
Enter the correct line voltage
If set to 380V change to 460V (or appropriate voltage per your application)
The ATV320 drives to trip on OSF faults on powerup?
Product Line:
ATV320
Environment:
All serial numbers
Cause:
Can not clear fault
Resolution:
To clear the OSF fault on powerup:
Set UrES [Mains voltage] to correct value of the line supply voltage.
Parameters described can be accessed by:
DRI- > CONF > FULL > FLT- > CLL
USb- [UNDERVOLTAGE MGT] > enter
UrES [Mains voltage] > enter
Enter the correct line voltage
If set to 380V change to 460V (or appropriate voltage per your application)
Опубліковано для: Schneider Electric Україна



