Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Why am I getting very frequent "a valid license not found" error in PME (Power Monitoring Expert).

Issue:
Very often PME machine encounters a licensing error. Once you restart Flexnet Licensing services then the issue resolves but again appears after a few days.

Product Line:
Power Monitoring Expert 8.x, Power Monitoring Expert 9, Power Monitoring Expert 2020

Environment:
Power Monitoring Expert licensing

Cause:
This issue is most likely to happen due to system date and time change. The licenses can become untrusted if there is a time change greater than about 5 minutes. It does not matter whether the time is changed manually or by auto-sync.

Resolution:
Investigate the auto time synchronization settings if the time is not changed manually. Check Windows System event log and there you are supposed to find entries like the one shown in the below screenshot.


Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Спільнота Schneider Electric
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings