How to enable or disable the 2G (GSM) network on a HMIBSC ?
Question
How to enable or disable the 2G (GSM) network on a HMIBSC ?

Description

If the 3G and 4G are not available in your area, the 4G LTE module will attempt to search for a valid 2G network.

This action require a lot of HMIBSC resources and  require a lot of electrical power.

To disable the 2G network research :
1- Open a HMIBSC prompt with the admin/root account
2- Reach the LTE module communication interface : microcom –s 115200 /dev/ttyACM0
3- Disable the 2G network: AT+URAT=6,3  //UMTS and LTE mode; LTE firstly

To enable the 2G network research :
1- Open a HMIBSC prompt with the admin/root account
2- Reach the LTE module communication interface : microcom –s 115200 /dev/ttyACM0
3- Enable the 2G network: AT+URAT=4,3  //GSM, UMTS and LTE mode; LTE firstly

Keywords
HMIBSC, IIOT edge box, LTE module, 2G, 3G, 4G, GSM, UMTS, LTE, Linux

Product Family
IIOT edge box

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings