Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
How is calculated the processor load value in the BMXNOC0401 communication module?
Issue:
How is calculated the Processor load value in the BMXNOC0401 communication module?

Product Line:
M340
BMXNOC0401

Environment:
Web page

Resolution:
Processor load value is a ratio between “CPU non-Idle tasks Time” and “Total CPU time”( if idle is 30% then CPU utilization is 100-30=70%).
The CPU is a multi-task system, the execution order of the different type of tasks depend on their priorities .
In the case of the BMXNOC0401, the following tasks have an impact on its load :
  • Server and client traffic packets per second as each packet is inspected and a transaction occurs
  • Size of I/O scanner image: bigger the scanner load, the longer it takes to copy from the xbus
  • PLC CPU scan time, as we have to transfer the I/O scanner twice a scan cycle.
  • General network traffic like multicast and broadcast traffic as it must be inspected

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings