Is there a way to find out what IP address the BOOTP server assigned to the NOC module?

To retrieve the IP address of the BMENOC without knowing in advance what it is, a READ_VAR request needs to be sent :

1- The configuration of the character string of the ADDMX should follow this rule : 'r.s.c{127.0.0.1}UnitID' , with :

  • r : rack number of the BMENOC
  • s: slot number of the BMENOC
  • c: channel to be used to communicate with BMENOC
  • UnitID : if UnitID is not 255, then you need to type in the number

In my example , my BMENOC is located in slot 3 of rack 0 , the string is '0.3.0{127.0.0.1}100'

Then the IP address used is the loopback IP address of the BMENOC module:127.0.0.1 .

2- Then send a modbus request to the BMENOC with the following parameters :

  • Enable : trigger
  • ADR : ADDM_TYPE with Unit ID =100
  • OBJ : '%MW'
  • NUM : 5
  • NB: 2
  • GEST : exchange management array of 4 INT, do not forget to define a timeout (3rd INT of the array)

The array RECP_NOC[1..2] contains the IP address of the BMENOC in hexadecimal format.

Schneider Electric Україна

Досліджуйте більше

Продукт:

Досліджуйте більше

Продукт:

Потрібна допомога?

Почніть тут!

Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

Звернутися до служби підтримки

Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

Де придбати?

Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

Переглянути відповіді на поширені запитання

Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.