What is the MODBUS Register Mapping of SNTP Diagnostics Data for CPUs and communication modules in M580?
SNTP Diagnostic data of 57 words, are available on CPUs and BMENOC0301/11 communication modules using Modbus function code 3 with the unit ID set to 100, offset Modbus Address 1218 and below is the MODBUS Register Mapping:
| Address | MS Byte | LS Byte | CIP Type | Comments |
| 1218 | MSW - MSB | MSW - LSB | Uint32 | Primary NTP Server IP Address |
| Offset + 01 | LSW - MSB | LSW - LSB | ||
| Offset + 02 | MSW - MSB | MSW - LSB | Uint32 | Secondary NTP Server IP Address |
| Offset + 03 | LSW - MSB | LSW - LSB | ||
| Offset + 04 | Unused | BYTE | Uint8 | Polling Period (in seconds) |
| Offset + 05 | Unused | BYTE | Uint8 | Update CPU with Module Time |
| Offset + 06 | MSW - MSB | MSW - LSB | Uint32 | Time Zone |
| Offset + 07 | LSW - MSB | LSW - LSB | ||
| Offset + 08 | MSB | LSB | Int16 | Time Zone Offset (in minutes) |
| Offset + 09 | Unused | BYTE | Uint8 | Daylight saving time bias (in minutes) |
| Offset + 10 | Unused | LSB | Uint8 | Daylight Saving Start Date - Month |
| Offset + 11 | Unused | LSB | Uint8 | Daylight Saving Start Date - week #, day of week |
| MS 4-bits: occurrence # (1 = 1st occurrence, 2 = 2nd occurrence…, 5 = fifth or last occurrence) | ||||
| LS 4-bits: day of the week (0 = Sunday…, 6 = Saturday) | ||||
| Offset + 12 | MSW - MSB | MSW - LSB | Uint32 | Daylight Saving Start Time (seconds elapsed from midnight) |
| Offset + 13 | LSW - MSB | LSW - LSB | ||
| Offset + 14 | Unused | LSB | Uint8 | Daylight Saving End Date - Month |
| Offset + 15 | Unused | LSB | Uint8 | Daylight Saving End Date - week #, day of week |
| Offset + 16 | MSW - MSB | MSW - LSB | Uint32 | Daylight Saving End Time (seconds elapsed from midnight) |
| Offset + 17 | LSW - MSB | LSW - LSB | ||
| Offset + 18 | Unused | BYTE | Uint8 | SNTP Mode |
| Offset + 19 | Unused | BYTE | Uint8 | Reserved |
| … | ||||
| Offset + 32 | Unused | BYTE | Uint8 | Reserved |
| Offset + 33 | MSW - MSB | MSW - LSB | UDINT | Network Time Service Status |
| Offset + 34 | LSW - MSB | LSW - LSB | ||
| Offset + 35 | MSW - MSB | MSW - LSB | UDINT | Link to NTP Server Status |
| Offset + 36 | LSW - MSB | LSW - LSB | ||
| Offset + 37 | MSW - MSB | MSW - LSB | UDINT | Current NTP Server IP Address |
| Offset + 38 | LSW - MSB | LSW - LSB | ||
| Offset + 39 | MSW - MSB | MSW - LSB | UDINT | NTP NTP Server Type |
| Offset + 40 | LSW - MSB | LSW - LSB | ||
| Offset + 41 | MSW - MSB | MSW - LSB | UDINT | NTP Server Time Quality |
| Offset + 42 | LSW - MSB | LSW - LSB | ||
| Offset + 43 | MSW - MSB | MSW - LSB | UDINT | Number of NTP Requests Sent |
| Offset + 44 | LSW - MSB | LSW - LSB | ||
| Offset + 45 | MSW - MSB | MSW - LSB | UDINT | Number of Communication Errors |
| Offset + 46 | LSW - MSB | LSW - LSB | ||
| Offset + 47 | MSW - MSB | MSW - LSB | UDINT | Number of NTP Reponses Received |
| Offset + 48 | LSW - MSB | LSW - LSB | ||
| Offset + 49 | MSB | LSB | UINT | Last Error |
| Offset + 50 | MSW - MSB | MSW - LSB | UDINT | Current Time |
| Offset + 51 | LSW - MSB | LSW - LSB | ||
| Offset + 52 | MSB | LSB | UINT | Current Date |
| Offset + 53 | MSW - MSB | MSW - LSB | UDINT | Daylight Savings Status |
| Offset + 54 | LSW - MSB | LSW - LSB | ||
| Offset + 55 | MSW - MSB | MSW - LSB | DINT | Time Since Last Update |
| Offset + 56 | LSW - MSB | LSW - LSB |
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.