Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Cannot access the PowerChute Business Edition version 10.0.2 Agent web interface.
Issue:
Cannot access the PowerChute Business Edition version 10.0.2 Agent web interface. This may arise after upgrading from version 10.0.1 or a clean install. Also, you may see Windows Event ID 1067, and in the pcbe.log found in C:/Progarm Files (x86)/APC/PowerChute Business Edition/agent/log, you will see "Unable to load permanent storage m11.cfg.  If this file is corrupted, you may need to re-install".

Product:
PowerChute Business Edition version 10.0.2 Agent

Environment:
All supported Windows OS

Cause:
Security changes made to Agent 10.0.2

Solution:
Uninstall PowerChute Business Edition 10.0.2 and install PowerChute Serial Shutdown, available at
https://www.se.com/ww/en/product-range/137943580-powerchute-serial-shutdown

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings