Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Cannot run multiple instances of the PLC simulator.

Attempts to run multiple instances of the PLC simulator  returns the following error.
1

The reason the error is returned is due to the default TCP/IP port 502 for the simulator to have been already used.  To resolve the issue,
a different TCP/IP port must be used for any additional instance of the PLC simulator.


The following steps can be used to run multiple instances of the PLC Simulator.

  • Click on Start\Windows System.
  • Select 'Command Prompt.

2



Change the path to the folder that the PLC simulator is installed.   In this example, I have copied the PLC simulator folder to my root C: drive.

Type in the following command for each instance of the simulator.

sim /IP(Ipaddress) /Port(TCP/IP port number)

i.e., C:\PLC_Simulator>sim /IP127.0.0.1 /PORT503

3


  • Start the the Control Expert applications
  • Connect to each simulator using the IP address and port number for the applicable instance of the simulator.

i.e., 127.0.0.1:503

4
5

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings