How to deactivate the User Rights only for the Web Visualization on M241/251 and M262 controllers?

As from EcoStruxure Machine Expert V2.0, it is possible to deactivate User Rights for the Web Visu only on M241/251 and M262 controllers.
That means User Rights remain active for other services.

To do it, User must create the empty file WebVisuNoLogin.cfg into the folder /usr/Visu and reboot the controller.

After this action, no password is required to connect to the web visualization.

WebVisuNoLogin.cfg file can be downloaded to the controller through FTP Server connection or from EcoStruxure Machine Expert (MyController >> Files tab).


Through FTP Server connection:
FileZilla


From EcoStruxure Machine Expert:
Machine Expert

Important:

Since Machine Expert V2.3, due to the new implementation of the User Management in the Visualization Manager, it is needed to Convert it to Legacy implementation to continue using this solution. By default, the implementation mode is set to Runtime based.

Convert_to_legacy

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings