Can I use the READ_REMOTE EFB to read data from located or unlocated variables in a Premium PLC?


Issue:
Using the READ_REMOTE EFB to read data from unlocated variables in a Premium or Quantum PLC


Product Line:
EcoStruxure Control Expert


Resolution:
Yes. The READ_REMOTE block will read data from a remote Unity Premium PLC. In the Premium PLC, Data dictionary must be enabled. And in the M340 or M580 PLC where the READ_REMOTE block reside, the second word of the CTRL pin of the READ_REMOTE block must have a value of 1

Setup of the READ_REMOTE blockread_remote_premium.PNG


Premium PLC with data in unlocated variables.
read_remote_premium2.PNG

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings