Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
What does the diagnosis LED ON mean on TeSys Giga contactors ? How many on/off operations left after the LED is ON ?
The diagnostic LED shall be ON,
  1. when the contactor (switching module) reaches its end of life, means it have reached 85% of its electrical life. The electrical life depends on the operational voltage and current, utilisation category, make break current (AC3/AC3e) and depends on application type. So, the remaining number of operations shall also vary depending on multiple factors : 1 beat
  2. Coil undervoltage (A1-A2 <0.8Uc): 2 beats
  3. Coil overvoltage (A1-A2 )1.1Uc): 3 beats
  4. Internal fault: continuous beats
  5. Remote wear diagnosis (RWD) module (only when Advanced version) cannot enable remote alarm for central monitoring: 4 beats
Note that detail information refers to installation guide DOCA0189EN and here is the link: TeSys Giga Series - Contactors and Electronic Overload Relays - Installation Guide User guide | Schneider Electric

Schneider Electric Україна

  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings