Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
PME2020/PME2021 Use my windows credentials fails with "The user name or Password you entered is invalid"

_____________________________________________________________________________________
Section 1 – Product /System/Environment information

PME2020
PME2021
_____________________________________________________________________________________
Section 2 – Issue

Logging in the WebClient Using my windows credentials fails with "The user name or password you entered is invalid"
_____________________________________________________________________________________
Section 3 – Root Cause

If the Windows Authentication setting is disabled in IIS for the default website, the one-click option won't work.

aa

_____________________________________________________________________________________
Section 5 – Troubleshooting/Proposed Solution
Enable the Windows Authentication setting  in IIS for the default website
Reset IIS and the one-click option will work.

Schneider Electric Україна

  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings