Чим ми можемо вам допомогти сьогодні?

Why, after an application full download, some Modbus I/O scanning variables written to devices and driven by a BMENOC03x1 are not correct (bytes swapped) ?

This problem is a known issue and fixed in firmware revisions :
- SV1.05 for BMENOC0321
- SV2.16 for BMENOC0301 and BMENOC0311

The issue occurs when all conditions below are met :
- when using firmware revisions lower than the ones described above
- when re-configuring and re-downloading application with a Modbus IO Scanner configuration into a BMENOC3xx (without doing a power cycle after the download)
- IO Scanner configuration contained a mix of "Read ONLY", "Write ONLY" and "Read/Write" modbus request
- some IO Scanner lines have been deleted and/or added

=> These four conditions may cause byte swapped data (for little endian conversion) on some modbus commands on the I/O scanning devices.

A global power cycle on the rack or hot swap of BMENOC03x1 makes the issue disappear.

We recommend to upgrade the BMENOC03x1 firmware to the latest available version.

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings