How to upload and convert a Modicon Micro 110CPU612xx Modsoft application to Unity.

Use the following steps to upload the application using Modsoft:

  • Start Modsoft.
  • Click on Transfer
  • Select 'PLC to File'.
  • Select 'New Program'.

image.png

  • Type in a filename.
  • Hit ENTER

image.png

  • Type in a location for saving the application or just use the default location.
  • Hit ENTER

image.png

  • Type in the Modbus address.
  • Hit Enter.

image.png


  • Select the Modbus I

image.png


  • Select RTU for the mode.

image.png


  • Select Even for the parity

image.png


  • Select the Stop Bit.

image.png


  • Select the baud rate.

image.png


  • Select the appropriate COM port on the PC.
    • Wait for the upload to finish.
    • Save the changes.

    image.png


    • Start
    • Open the application with Unity using the 'Modsoft projects' selection.
    • Save the Unity application.

    image.png

    image.png

    • Select the PLC type to convert to:
    • Click on OK.

    image.png

    Schneider Electric Україна

    Досліджуйте більше

    Досліджуйте більше

    Потрібна допомога?

    Почніть тут!

    Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

    Звернутися до служби підтримки

    Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

    Де придбати?

    Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

    Переглянути відповіді на поширені запитання

    Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.