Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Important setting to know from OPCUA Client ?
It’s important to know the following information when there is problem on the OPCUA protocol between the OPCUA client and the OPCUA Server:
We need to know:
  • Simple architecture of the whole system between OPCUA Client and Server and other Network connection
  • OPCUA Client: which SCADA, what is the OPCUA Stack (From OPC Foundation, Unified automation, …), How it is developped the OPCUA client (C#...)?
  • Subscription setting:
    • LifeTimeCount configured from OPCUA client
    • Publishing Interval configured from OPCUA client
    • Session Timeout configured from OPCUA client
  • Monitored Item Setting
    • Sampling Interval configured from OPCUA client
  • Mast Cycle time of the PLC
Example from UaExpert :
  • Subscription setting:
subscription
  • Monitored Item Setting
Setting Monitoring Item

Schneider Electric Україна

Досліджуйте більше
Продукт:
Серія:
Досліджуйте більше
Продукт:
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings