Is it possible replace a PRM without Control Expert?
Yes, it is possible.
In theControl Expert application, under PRM general settings, ensure the following options are checked and properly configured:
- Create an entry for this device name in the DHCP server
- Backup the PRM configuration in the FDR server on download
Once these settings are confirmed, follow these steps to correctly replace the PRM:
- Remove the PRM module to be replaced.
- Prepare the new PRM module:
- Set its lower rotary switch to ‘E’ (Configuration file deletion) to clear any existing configuration.
- Power up the new PRM and wait for the boot process to complete, then power it off.
- Match the rotary switch positions:
- Check the rotary switch positions on the old PRM and set the new PRM identically.
- Install the new PRM:
- Power up the new PRM in the same location as the old one.
The new PRM will boot and automatically retrieve its configuration file from the FDR server.
Опубліковано для: Schneider Electric Україна
Досліджуйте більше
Продукт:
Досліджуйте більше
Продукт:
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.