Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Unable to access NMC3 via HTTPS using Chrome - ERR_CERT_INVALID

Problem:
Users are unable to access an NMC3 with a self-signed certificate via HTTPS using recent versions of the Google Chrome browser

Environment:
UPS Network Management Card 3 - AP9640/41/43
Devices that use an embedded NMC3, including but not limited to PDU (2022+ model AP8xxx, APDU9xxx), ATS (AP44xxA), and Smart-UPS/Symmetra UPS systems

Cause:
A recent Chrome update is blocking the self-signed certificate ECC certificate that is used by default on an NMC3.

Resolution:
This will be addressed in a future version of firmware, and this article will be updated when a fix version is available.

Please note that this issue is fixed from firmware rev. 2.4, so updating firmware should be fist step in the troubleshooting process.

Secondary workarounds are:

  • Use a different browser
  • Use an older version of Chrome
  • Delete the ECC self-signed certificate on the NMC and generate an RSA cert. The commands can be performed via the CLI:
    • apc>ssl key -d
    • apc>ssl key -rsa [1024|2048|4096]
  • Use the CLI Security Wizard and a 3rd party certificate authority to create a signed certificate


Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Спільнота Schneider Electric
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings