Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
How Can I select Gateway/Bridge Device option in IOSCANNING for M580 CPU ?

Issue:

How Can I select Gateway/Bridge Device option in IOSCANNING for M580 CPU ?

Product Line:

M580

Environment:

EcoStruxure Control Expert

Resolution:

User needs to install EcoStruxure Control Expert 15.1 or higher version and choose the CPU version as SV3.20 or higher in hardware configuration .

2.JPG

Select the check box to enable this feature. The communication module doubles the timeout setting by increasing the number of re-transmissions to 6 (instead of the typical setting of 3).

1.JPG

Here is one demo wireshark trace when M580 reset the TCP connection after 6 times TCP retransmissions without receiving the response of ModbusTCP server device after Gateway/Bridge Device option is selected.

3.JPG

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings