How to disable alarm redirection from script
Below is an example showing how alarm redirection may be disabled from a mimic script. The script retrieves a list of all points in the database that contain "Script Disable Alarm Redirection" in their full names and disables alarm redirection for each point in the list.

DISCLAIMER: Please note this is an example only and should only be used in a test environment. The script should not be used on a live production system without making the necessary adjustments and testing for each application.
Sub DisableAlarmRedirection

Dim DGRS, DGRSRows, DGRSColNames, oPoint

Set DGRS = Server.Query("SELECT FULLNAME FROM CDBPoint WHERE FullName LIKE '%Script Disable Alarm Redirection%'")

If Not(DGRS.Error) Then
    DGRows = DGRS.Rows
    DGColNames = DGRS.ColumnNames
    For r = 0 To (DGRS.RowCount - 1)       
        Set oPoint = Server.FindObject(DGRows(r,0))
        oPoint.Interface.AlarmRedirection=False            
    Next
Else
    Msgbox DGRS.ErrorMessage, vbCritical + vbOKOnly, "Error in SQL Command" 
End If

End Sub

Schneider Electric Україна

Досліджуйте більше
Продукт:
Досліджуйте більше
Продукт:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings