Why can't I download to a brand new HMIGTO / HMIGK with Vijeo Designer 6.2 SP11 or older?
Issue
Can't download to a new HMIGTO / HMIGK using Vijeo Designer v6.2 SP11 or older.
Product Line
HMIGTO and HMIGK families of HMIs
Environment
Vijeo Designer v6.2
Cause
The new HMIGTO/HMIGK families have a hardware component change that requires newer Vijeo Designer versions.
Resolution
The Harmony HMIGTO and HMIGK families of HMIs withSV4.0 or later on the sticker on the back of the HMI need to be programmed with Vijeo Designer v6.2 Service Pack 12 minimum.
Please find the download links for SP12 here:
https://www.se.com/us/en/faqs/FAQ000239885/
The Harmony HMIGTO and HMIGK families of HMIs withSV5.0 or later on the sticker on the back of the HMI need to be programmed with Vijeo Designer v6.3 minimum. Note: Vijeo Designer v6.3 requires a new license.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Опубліковано для: Schneider Electric Україна
Потрібна допомога?
Почніть тут!
Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.
Звернутися до служби підтримки
Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Переглянути відповіді на поширені запитання
Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.