Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
PowerChute Network Shutdown v4.5, v5.x reports Unable to connect to Cloud Licensing Server.
Issue:
When attempting to connect to the PowerChute Licensing Server, the software reports, "Unable to connect to Cloud Licensing Server. Please verify you have internet access and try again."

Product:
PowerChute Network Shutdown

Environment:
PowerChute Network Shutdown version 4.5, 5.x for Hyperconverged and Virtual Infrastructure;
Examples: PowerChute for VMware ESXi with vCenter Server, Microsoft Hyper-V

Cause:
Network connectivity

Solution:
  1. Verify the PowerChute server can reach the internet. If it cannot, you must use the activate offline method.
  2. Verify the proxy server settings are correct if in use.
  3. If a proxy server is not in use, ensure all entries for proxy information are blank. By default, PowerChute ships the port number filed in. Port 80. That information must be removed/deleted.

Unable to connect to server

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings