Чим ми можемо вам допомогти сьогодні?

How to configure PowerChute to power on automatically after a power outage without VMware High Availability or Autostart.

Article available in these languages:

  • French

Issue:
PowerChute VM fails to start with the ESXi host after power is restored.

Product Line:
PowerChute Network Shutdown v5.0.

Environment:
PowerChute Network Shutdown v5.0 configured with vSAN/VMWare or any HCI support

Cause:
Per VMware recommendations, HA is disabled during shutdown. This will prevent HA from restarting the PowerChute VM.

The VMware Auto-start policy cannot be used in HCI environments where cluster services must be available before VMs can be powered on. If Hosts are in maintenance mode on start-up, this will also prevent the Auto-start policy from powering on the PowerChute VM.


Solution:

Discontinue using PowerChute Network Shutdown v5.0, install PowerChute Network Shutdown v5.2 via the link below, and select "See Software". https://www.se.com/us/en/product-range/61933-powerchute-network-shutdown/104358239448-powerchute-subscriptions/#overview

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings