If RemoteConnect project was created with older version then Logic Library must be updated.
Here are the steps for library update from RemoteConnect:
1. Open project in RemoteConnect and then open x70 Ladder Editor
2. Select "Tools" and then "" and observe <LibSet V11.1>

3. Right click on "LibSet" and then "Compare Project with Library ...!

4. In "LIBRARY Version Management: select "Update All" and then follow the steps.

5. Update and build the project
6. Close and open the RemoteConnect project.
7. Click on Update Logic Library and then YES to proceed with upgrading LibSet V11.1 to V15.1


8. Verify that now when Types Library Manager LibSet is V15.1
Here are the steps for library update from RemoteConnect:
1. Open project in RemoteConnect and then open x70 Ladder Editor
2. Select "Tools" and then "" and observe <LibSet V11.1>
3. Right click on "LibSet" and then "Compare Project with Library ...!
4. In "LIBRARY Version Management: select "Update All" and then follow the steps.
5. Update and build the project
6. Close and open the RemoteConnect project.
7. Click on Update Logic Library and then YES to proceed with upgrading LibSet V11.1 to V15.1
8. Verify that now when Types Library Manager LibSet is V15.1
Опубліковано для: Schneider Electric Україна


Потрібна допомога?
Інструмент вибору продукту
Швидко та легко знаходьте потрібні продукти й допоміжне обладнання для своїх завдань.
Розрахувати вартість
Ставте свої запитання щодо продажів онлайн, і з вами зв’яжеться фахівець
Де придбати?
Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.
Довідковий центр
Знайдіть усі необхідні ресурси для підтримки в одному місці.