Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
How do I start-up/turn on BE900G3 and BE1050G3?

Issue:
How do I start-up/turn on BE900G3 and BE1050G3?

Product Line:
BE900GE and BE1050GE

Environment:
All Serial Numbers


Steps / Procedures:

1. Connect the internal battery (
The Back UPS is shipped with one battery cable disconnected).

Follow the series of steps stated below:

Connect battery first.JPG


2. And when the battery is connected successfully, plug it into the Utility or AC main source.
wall outlet connection
3. Press the POWER button. It will illuminate green, and a single short beep indicates that the Backups is on and helping to provide protection for connected equipment.
turning on


Additional inputs:

* Self-Test only occur upon start up.
* Intentional manual self-test is not applicable for this particular product.
* Battery replacement for Backups BE900G3 is RBC17 and BE1050G3 is APCRBC164.

Schneider Electric Україна

  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Спільнота Schneider Electric
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings