Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
PME 2024, 2024R2: EPSS report subscription throws deserialize argument error

Environment:

Power Monitoring Expert 2024 and 2024R2

----------------------------------------------------------------------

Product Line:

EPSS Report

----------------------------------------------------------------------

Description of the issue:

After upgrading from an older version of PME, a saved EPSS report subscription throws a deserialize argument error as it is shown in the attached screenshots below.

Image

Image

Image

----------------------------------------------------------------------

Cause:

The EPSS report template includes some new parameters that were not present in the older versions of PME. So, when the subscription runs and it references the new template, it finds missing parameter data. This causes a deserialization error.

Workaround:

Open the saved report in Web Reporter and re-save the same report. This will add all the missing parameters.

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings