Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
Disabling TLS 1.3 in Geo SCADA Expert (August 2024 Update and Later)

⚠️*Warning: This article contains information about editing the registry. Improper changes to the registry can permanently damage the operating system.
Always backup the registry before making any changes.*

Starting with the Geo SCADA Expert August 2024 update, a new registry setting was introduced that allows users to disable TLS 1.3 specifically for Geo SCADA, without impacting the system-wide TLS configuration managed by Schannel.

To (temporarily) disable TLS 1.3 on a Geo SCADA server, follow these steps:

  1. Open the Registry Editor (regedit).
  2. Navigate to the following key:
    HKEY_LOCAL_MACHINE\SOFTWARE\Schneider Electric\ClearSCADA\SCXCom
  3. Create a new String Value named:
    EnableTLS13
  4. Set its value to:
    - "False" to disable TLS 1.3
    - "True" to enable TLS 1.3 (default behavior)

Note: This registry key is not created automatically. If it is missing, Geo SCADA will treat it as "True" by default.

Schneider Electric Україна

Досліджуйте більше
Продукт:
Досліджуйте більше
Продукт:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings