Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
How to Retrieve Maintenance Log from PowerLogic P5 Relay

Article available in these languages: Spanish

Issue:

Need to obtain the internal maintenance log file from an PowerLogic P5 relay for troubleshooting or analysis.

Product:

PowerLogic P5 Protection Relay

Environment:

  • PowerLogic P5 relay
  • Latest eSetup Easergy Pro software (downloadable from Schneider Electric website)
  • PC connected to the relay via front USB port
  • Relay powered off (HMI should display “5V USB only”)

Cause:

Maintenance logs are stored internally in the relay and require specific steps and credentials to access.

Resolution:

1.-Download and install the latest eSetup Easergy Pro software from Schneider Electric’s website.

2.- Ensure the relay is not powered on. Connect the P5 relay to the PC using the front USB port.

1

3.- Wait until the relay HMI displays “5V USB only”.

4.- In Easergy Pro, click Read Maintenance Log File.

2

5.- Log in using the following credentials:

Login: InstallerLevel

Password: AAAA

3

6.- Save the log file to your desired location. The file will have the extension .p5I.

4

7. - Send the .p5I file to the Advance Tech support team for further analysis.

5

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings