How to Properly View Downloaded Log Files from the SAGE RTU

Issue:

Downloaded Log files from the SAGE RTU Graphic User Interface (GUI) appear in unreadable characters (e.g., Chinese symbols) when opened in standard text editors like Notepad.

Product:

Sage RTU Series (SAGE 1X10, 1X30, 1X50, 2X00, 3030X)

Environment:

  • SAGE RTU GUI
  • Windows OS (using default Notepad)
  • Log files downloaded from RTU

Cause:

The issue occurs because the files use UTF-8 encoding, and standard Notepad does not properly interpret this encoding by default, resulting in unreadable characters.

Resolution:

  1. Use a text editor that supports UTF-8 encoding, such as Notepad++ (recommended).
  2. If the file still shows NULL or strange symbols:
    • In Notepad++, go to Encoding → Convert to UTF-8.
    • Save and reopen the file; it should display correctly now.
  3. Alternative applications:
    • WordPad
    • Spreadsheet viewers (e.g., Excel)
  4. Ensure the file is not corrupted before conversion.

Example, Using Notepad:

1

Using NotePad++:

2

Using a spreadsheet viewer:

3

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings