Наші бренди

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.
		
Чим ми можемо вам допомогти сьогодні?
How to Calculate the Resistor Value for Open Wire Detection in BMXSDI1602 using DDP 2 or 3 wires?

Issue

Open wire detection in BMXSDI1602 requires to create artificially a leakage current (Ileakage) on the line with a resistor in parallel to the sensor. If this leakage current (0.4 mA < 1.3 mA) is out of range, the external line is considered as cut (or in a short-circuit to ground condition).

Resolution

For a dry contact sensor, set in parallel with the sensor a Rext = 33 K Ω.

However, using DDP 2 or 3 wires, the leakage current needs to fall within the limits defined above. You need to define the value of the resistor (Rext) to set in parallel with the sensor, considering

  • the natural leakage current of the sensor
  • the Rint (internal resistor) of the input, equal to 7.5 K Ω

Then, in order to obtain a current in the range of  :for1

for2

for3

The calculation of Rext is performed with the following formula :

for4

where :

for5

Schneider Electric Україна

  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings