My Smart UPS Modular Ultra has an Unknown UPS internal error (1568-00B0) or Unknown UPS internal error (156A-00B0) alarm.

Purpose:

If you update your UPS to FW 15.0 or later and you have an SBU (Service Bypass Unit) connected, you may see an Unknown UPS internal error (1568-00B0) or Unknown UPS internal error (156A-00B0) alarm.


Product Line:

Smart UPS Modular Ultra


Environment:

All models, all serial numbers on UPS Firmware 15.0 or later with an SBU (Service Bypass Unit) connected.


Resolution:

UPS Firmware 15.0 and greater supports new events for the SBU switch positions.  In order to see the correct alarm messaging on the display and NMC, please upgrade the NMC/Display to the latest firmware.  See below for FAQs on the different ways to upgrade that firmware.

How to Install the Smart-UPS Modular Ultra NMC/Display Firmware using the USB Port
Web link - https://www.apc.com/us/en/faqs/FAQ000261841/

How do I update my Smart-UPS firmware using the web interface of my Network Management Card?
Web Link - https://www.se.com/ca/en/faqs/FA170679/

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings