VMs are not available in the PowerChute priority list.

Issue:

VMware VMs are not shown in the PowerChute priority list.

Product:

PowerChute Network shutdown

Environment:

VMware vCenter Server

Cause:

The VMs have been added to a VMware resource pool.

In the example below, VM AlmaLinux9A and Azure23HCI have been added to resource pool 1

vCenter Server list of VMs

When viewing VMs in the PowerChute priority list, the AlmaLinux9A and Azure23HCI are not displayed.

PowerChute UI not showing the resource pool VMs

NOTE: VMs added to a resource pool will be powered off along with unprioritized VMs.

Solution:

To prioritize VMs that have been added to a resource pool, create a vApp or vApps within the resource pool and add the VMs to the vApp(s)

In the example below, we have created a Test vApp within the resource pool and added the two VMs to that vApp. The vApp has been added to a high-priority group in PowerChute so the VMs will be shutdown last and started first.

PowerChute showing the vApp that was added to the resource pool

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміщення продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва
  • Де купити
  • Спільнота Schneider Electric
  • Запит цінової пропозиції
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • EcoStruxure
  • Вакансії Пошук
  • Блог
  • Загальні умови ведення бізнесу
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings